Generator Set Specifications
Minimum Rating 180 kVA / 144 kW
Maximum Rating 200 kVA / 160 kW
Emissions/Fuel Strategy EU Stage IIIA emissions compliant.
50 Hz Prime 180 kVA / 144 kW
50 Hz Standby 200 kVA / 160 kW
Frequency 50 Hz
Speed 1500 RPM
Voltage 220-415 Volts
50 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating Standard reference conditions 25C (77F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine Specifications
Engine Model Perkins 1106D-E70TAG4
Bore 105 mm (4.1 in)
Stroke 135 mm (5.3 in)
Governor Type Electronic
Displacement 7.0l (427.8 cu. in)
Compression Ratio 16.8:1
Standard Equipment
Engine
Air Cleaner
Lube oil drain valve
Engine filled with lubrication oil
High Coolant Temperature Shutdown
Low Oil Pressure Shutdown
Cooling
Package mounted radiator
Radiator & Cooling Fan
Coolant Drain Valve
Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
Cooling System filled with Coolant mix
Exhaust
Exhaust flange outlet
Exhaust stub pipe and gasket
Fuel
8 Hr Fuel Tank
Fuel Fittings for Local and Remote Feed
Alternator
FG Wilson FGL Alternator
SHUNT Excitation
IP23 Protection
Control Panel
PowerWizard 1.1
Mounting
Base, Formed Steel with Single wall Fuel Tank
Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
Anti-vibration mounts
Battery Tray and Cables
There are no reviews yet.